Direct-on-line starting of a DC motor draws 15 to 20 times rated current because there is no back-EMF yet. This page explains the physics, gives a step-by-step resistor calculation, and shows when to short out each step.
At standstill the back-EMF Ea = Ce·Φ·n is zero, so only the small armature resistance Ra limits the inrush. With Ra of a few tenths of an ohm, applying full 220 V would draw 15 to 20 times rated current, burning brushes and shocking the shaft train. The fix is to limit inrush to roughly 2 to 2.5 times rated current by inserting resistance in the armature circuit.
A practical scheme uses two to four resistor steps. Size the total resistance R1 = U/I1 − Ra with I1 at twice rated current, then short out each step when the current falls back to about 1.2 times rated, giving a current ratio of about 1.67 per step. For a 220 V, 40 A motor with Ra = 0.5 Ω the total comes to 2.25 Ω, split across three steps near 0.85, 0.5 and 0.9 ohm.
Cut-out can be current-controlled, using accelerating current relays, or time-controlled with 0.5 to 3 s delays per step. Current control follows the load better; timing is simpler to wire. Starting resistors are short-time rated, so never leave them in circuit as speed regulators, and verify the allowable starts per hour for frequent duty.
| Method | Power range | Inrush multiple | Notes |
|---|---|---|---|
| Direct on line | Below 0.5 kW | 15~20 times | Small motors only |
| Stepped armature resistor | Small to medium | 2~2.5 times | Classic, short-time resistor |
| Reduced voltage | Larger machines | About 2 times | Needs adjustable DC source |
| Field first, armature later | General | Within 2 times | Energise field before armature |
| Starting resistor as speed regulator | Forbidden | Unlimited | Thermal rating too small |
Remember the order: field on first, then armature, always through resistance. Measure Ra by the voltmeter-ammeter drop method, size the total for twice rated current, cut in two or three steps at 1 to 2 s intervals, and consider the job done when the ammeter swings between 1.2 and 2 times rated.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 1311 for DC machine testing and IEC 60204-1 for machinery electrical safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.