Star vs delta connection of three-phase systems compared

Star and delta differ by one letter but three times the power. This page lays out the voltage and current relations, nameplate reading, and what happens when the links are in the wrong row.

1. How it works

Star (Y): winding ends join at a common point, line voltage is √3 times phase voltage (380V vs 220V), line current equals phase current. Delta (△): windings close nose-to-tail, line voltage equals phase voltage, line current is √3 times phase current. The decisive consequence: on the same supply the same motor in star develops one third of its delta power and torque - the basis of star-delta starting and of every miswired surprise.

2. Practice and pitfalls

Read the nameplate first: 380V △ means delta on a 380V grid; 380/660V △/Y means delta on 380V, star on 660V. In the terminal box, delta uses vertical link bars joining the three columns, star uses one bar across one row. A 7.5kW four-pole motor draws about 15A line current in delta with 8.7A in the windings; wrongly in star it delivers 2.5kW and stalls under load. Wrongly in delta, a star-rated motor sees √3 times the phase voltage and smokes within minutes. After any re-connection, run it unloaded: no-load current should be 30 to 50 percent of rated.

3. Star vs delta quick table

ItemStar (Y)Delta (△)Note
Line vs phase voltageLine = √3 × phaseLine = phaseWhere 380/220 come from
Line vs phase currentLine = phaseLine = √3 × phaseDelta windings carry less
Power of same motor1/3 of deltaReferenceBasis of Y-△ starting
Typical nameplate660V Y or 380/660380V △Read before wiring
Miswire outcomeDelta motor in star: 1/3 powerStar motor in delta: burnoutVerify with no-load current
Typical useHV motors, light startsStandard LV motorsFollow the nameplate

4. Notes

Motto: nameplate first, links second, no-load current third. After any change, the unloaded current must sit at 30 to 50 percent of rated - anything else means the links are wrong.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machine ratings per GB/T 755; standard voltages per GB 156; installation safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Delta motor wired in star:a third of the power, stall current cooks it
② Star-rated motor wired in delta:√3 times winding voltage, smoke in minutes
③ Fixed star-delta changeover time:switching before full speed, near-DOL inrush

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.