Fuse I²t characteristics and how to verify selectivity with them

I²t is the energy language of fuses - master it and coordination, semiconductor protection and cable checks all become one calculation. This page defines the terms and works three verifications.

1. How it works

I²t (A²s) is the thermal energy the fuse lets through, split into pre-arcing I²t (up to the instant of melting - the threshold of operation) and total I²t (pre-arcing plus arcing - the destructive energy passed on). At high prospective currents the values converge to constants, which makes them far more precise than time-current curves in the short-circuit region.

2. Practice and pitfalls

Three worked checks. Semiconductors: a thyristor rated 2500A²s behind a 63A fast fuse passing 1800A²s total - protected, with margin. Cables: withstand is S²K², so 10mm² copper XLPE takes 100×143² ≈ 2 million A²s against a 160A gG total of about 40000A²s - safe. Selectivity: downstream 63A total 15000A²s versus upstream 160A pre-arcing 30000A²s holds; but an upstream 100A with 12000A²s pre-arcing would beat the downstream fuse and black out the level above. Always verify with the actual brand datasheet - cross-brand spreads reach 30 percent - and keep the coordination table in the cabinet file.

3. Typical I²t values quick table (10kA prospective)

RatingClassPre-arcing I²tTotal I²t
25A gGGeneral purposeAbout 1200A²sAbout 2500A²s
63A gGGeneral purposeAbout 8000A²sAbout 15000A²s
100A gGGeneral purposeAbout 20000A²sAbout 35000A²s
160A gGGeneral purposeAbout 30000A²sAbout 55000A²s
63A fast aRSemiconductorAbout 1000A²sAbout 1800A²s
100A fast aRSemiconductorAbout 2000A²sAbout 4000A²s

4. Notes

Verification order: protect the semiconductor (total I²t under 80 percent of device withstand), protect the cable (under S²K²), then protect selectivity (downstream total under upstream pre-arcing). Clear all three and the scheme stands.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage fuses per GB 13539.1 (IEC 60269-1); semiconductor fuses per GB/T 13539.4; cable withstand per GB 50054. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Brand swap without recheck:30 percent I²t spread undoes years of coordination
② Downstream total I²t above upstream pre-arcing:the upstream beats the fault and blacks out a level
③ Sizing fast fuses on pre-arcing alone:arcing energy still damages the device

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.