I²t is the energy language of fuses - master it and coordination, semiconductor protection and cable checks all become one calculation. This page defines the terms and works three verifications.
I²t (A²s) is the thermal energy the fuse lets through, split into pre-arcing I²t (up to the instant of melting - the threshold of operation) and total I²t (pre-arcing plus arcing - the destructive energy passed on). At high prospective currents the values converge to constants, which makes them far more precise than time-current curves in the short-circuit region.
Three worked checks. Semiconductors: a thyristor rated 2500A²s behind a 63A fast fuse passing 1800A²s total - protected, with margin. Cables: withstand is S²K², so 10mm² copper XLPE takes 100×143² ≈ 2 million A²s against a 160A gG total of about 40000A²s - safe. Selectivity: downstream 63A total 15000A²s versus upstream 160A pre-arcing 30000A²s holds; but an upstream 100A with 12000A²s pre-arcing would beat the downstream fuse and black out the level above. Always verify with the actual brand datasheet - cross-brand spreads reach 30 percent - and keep the coordination table in the cabinet file.
| Rating | Class | Pre-arcing I²t | Total I²t |
|---|---|---|---|
| 25A gG | General purpose | About 1200A²s | About 2500A²s |
| 63A gG | General purpose | About 8000A²s | About 15000A²s |
| 100A gG | General purpose | About 20000A²s | About 35000A²s |
| 160A gG | General purpose | About 30000A²s | About 55000A²s |
| 63A fast aR | Semiconductor | About 1000A²s | About 1800A²s |
| 100A fast aR | Semiconductor | About 2000A²s | About 4000A²s |
Verification order: protect the semiconductor (total I²t under 80 percent of device withstand), protect the cable (under S²K²), then protect selectivity (downstream total under upstream pre-arcing). Clear all three and the scheme stands.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage fuses per GB 13539.1 (IEC 60269-1); semiconductor fuses per GB/T 13539.4; cable withstand per GB 50054. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.