Does a 100 A knife switch really carry 100 A of load? Not necessarily. This page explains the rating categories, load matching and derating rules that keep the blades from burning.
The nameplate current needs reading in three senses: rated thermal current for 8-hour duty, rated working current tied to a utilisation category, and short-time withstand for faults. Match accordingly: resistive loads run at full rating (AC-21), mixed loads with small motors at 80 percent (AC-22), and direct cage-motor switching at only 60 to 70 percent (AC-23), since breaking six-fold starting current erodes the blades badly. A 100 A switch run on a 30 A motor started frequently will blacken its blades within months.
Derating rules: 5 percent per 10 K above 40 C ambient, 10 to 15 percent inside cabinets, 0.5 percent per 100 m beyond 2000 m altitude, and 20 percent where manual operations exceed ten per hour. The blade grips the spring-loaded clips, and erosion lowers contact pressure in a vicious circle. Judge overload in the field with a thermal camera: a rise beyond 70 K at blades or terminals, blackened plating or annealed clip springs all say overcurrent or poor contact.
Install vertically with the handle up so gravity cannot close it; set the blade insertion depth per the maker, generally 15 to 25 mm; torque the terminals with spring washers. Operate decisively, since slow pulls draw arcs. Load breaking is only for small ratings (AC-22 up to 200 A); bigger switches isolate only, after the downstream breaker or contactor opens. Fuse-combination switches (HR series) add short-circuit protection with separately rated links.
| Load type | Category | Allowed ratio | Note |
|---|---|---|---|
| Resistive | AC-21 | 100% | Heaters, lighting boards |
| Mixed light duty | AC-22 | 80% | Small motors included |
| Cage motor direct | AC-23 | 60~70% | Further derate if frequent |
| Isolation only | None | Per rating | Open downstream first |
| In-cabinet mounting | None | Minus 10~15% | Poor ventilation |
| Hot ambients | None | Minus 5% per 10 K | Above 40 C |
Scan blades and terminals with a thermal gun on patrol and re-torque anything beyond a 70 K rise; recalculate the switch rating whenever the load changes; and keep the switching order strict: blades first on energising, last on de-energising, written on the operating ticket.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.3 (IEC 60947-3) for isolation switches and IEC 60204-1 for installation safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.