In the first tens of milliseconds after switch-on, inrush can hit 30 times rated current - tripping breakers and killing rectifiers. This page compares the NTC and the active bypass approaches.
At power-up the rectifier charges the bulk capacitor through only the line impedance, so a 1000W supply with 470µF on a 400V bus can draw 100 to 150A peaks. Two fixes: put a cold-high-resistance part in series (an NTC), or put a resistor in series for 100 to 300 milliseconds and then short it with a relay or thyristor.
The NTC costs a coin and needs no control, dropping to a fraction of its cold resistance within seconds and burning 0.5 to 2W steady state. Its fatal weakness: it needs 1 to 3 minutes to cool, so a hot restart offers no suppression at all - never use it on frequently cycled equipment. The active bypass repeats perfectly at every start: with 10Ω limiting the surge to 40A, the resistor absorbs roughly 38 joules per charge, well within a 10W wirewound. Watch for welded relay contacts - monitor the contact state or use a thyristor.
| Item | NTC thermistor | Resistor + relay bypass | Note |
|---|---|---|---|
| Suppression | Good cold, gone hot | Effective every start | No NTC on rapid cycling |
| Steady loss | 0.5~2W | Near zero | Bypass for big power |
| Recovery | 1~3 minutes after off | None needed | Check restart frequency |
| Cost | A few yuan | About 15 yuan with control | Including control circuit |
| Failure mode | Cracks open (safe) | Welded contact burns resistor | Monitor the bypass |
| Typical use | Appliances, small supplies | Drives, servos, industrial PSUs | Choose by cycling rate |
Decision line: once-a-day starts can live with an NTC; frequent cycling or high power demands the bypass. When tracing power-up trips on an NTC-equipped unit, first ask whether someone re-closed the breaker while it was still hot.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Inrush current limits per GB/T 17625.1 and the IEC 61000 EMC series; equipment safety per GB 4943.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.