A PLC output of 2 A cannot drive a contactor coil, and one signal must light three lamps at once. The interposing relay solves both. This page covers principle, selection and wiring practice.
Structurally a small contactor without an arc chute, the interposing relay carries 5 to 10 A contacts and exists to amplify signals: a PLC transistor output of 0.5 A energises the relay coil of 2 to 5 VA, and its 10 A contacts then drive the contactor. It multiplies contacts too, so one command drives indicators, sounders and interlocks in parallel, and it isolates circuits, letting a DC 24 V signal switch an AC 220 V path.
Selection parameters: contact rating (10 A resistive, 2 to 3 A at power factor 0.4 inductive), contact format such as 2NO/2NC or 4NO/4NC, coil voltage with DC 24 V the standard PLC companion and AC 220 V for power-side control, mechanical life beyond 10 million operations and electrical life near 100 thousand. Common types include Omron MY2NJ and MY4NJ, Schneider RXM, and domestic HH52P/HH54P socket types; versions with an indicator lamp and a flyback diode protect transistor outputs and ease troubleshooting.
Wiring rules: respect coil polarity on DC types and diode direction, suppress inductive loads with RC networks on AC or diodes on DC to spare the contacts, and follow the socket diagram exactly since reversed sockets burn coils instantly. Maintenance: replace contacts proactively at half electrical life on rapidly cycling circuits, test for welded contacts with a meter after de-energising, and route every PLC output through an interposing relay as standard practice, because a failed relay is a socket swap while a failed output card is downtime.
| Parameter | Typical value | Notes | Selection care |
|---|---|---|---|
| Contact rating | 10 A resistive, 3 A inductive | Convert by load type | Always derate inductive |
| Contact format | 2NO/2NC, 4NO/4NC | Choose per circuit | Keep a spare pair |
| Coil voltage | DC 24 V, AC 220 V | Match control supply | Polarity and flyback |
| Mechanical life | 10 million ops | Excludes contact wear | Reference only |
| Electrical life | About 100k ops | Load dependent | Halve for rapid cycling |
| Operate time | 5~15 ms | Fine for interlocks | Not a safety relay |
Number every relay on the drawing as KA1, KA2, fit indicator lamps across coils for patrols, keep the control voltage uniformly DC 24 V, and stock by contact format plus coil voltage, with MY2NJ-DC24V the universal spare. Series two contacts for critical interlocks against a single welded pair.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.5 (IEC 60947-5) for control relays and IEC 60204-1 for control circuit design. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.