Screw-in (RL1) and plug-in (RC1A) fuses look different and behave very differently. This page contrasts structure, performance and duty, so repairs and replacements stay safe.
The plug-in RC1A consists of a porcelain lid and base with the fuse wire clamped across the lid; it is the cheapest and simplest, but has no arc quenching medium, so its breaking capacity is only 1.5 to 3 kA at 380 V with scattered pre-arcing times. The screw-type RL1 seals its element inside a cartridge full of quartz sand, which splits and cools the arc, reaching 25 to 50 kA, and carries a red trip indicator in the cap.
RL1 spans 15 to 200 A with element tolerance inside 10 percent and a real current-limiting effect, fitting distribution feeders and motor circuits. RC1A spans 10 to 100 A with no limiting, wide fuse-wire variability depending on how tightly it is fitted, and suits only the last small lighting and heating circuits. Safety differs too: RL1 swaps a sealed cartridge with the cap, while RC1A puts fingers near live blades, and RL1 shows its state on the cap instead of an opened lid.
Today RC1A is obsolete and must not appear in new designs, with survivors in old buildings and small workshops; RL1 itself is giving way to RT18 cylindrical and RT0 types rated 50 kA. When replacing, re-verify breaking capacity, RC1A to RL1 gains an order of magnitude but never the reverse, recalculate element ratings for the load, and change oxidised old porcelain bases together with the fuse.
| Item | Plug-in RC1A | Screw-type RL1 | Note |
|---|---|---|---|
| Breaking capacity | 1.5~3 kA | 25~50 kA | An order apart |
| Current limiting | None | Yes | RL1 shields downstream |
| Blown indicator | None | Cap indicator | Easier patrols |
| Replacement | Pull lid, rewire wire | Swap sealed cartridge | RL1 safer |
| Element accuracy | Wide scatter | Within ±10% | RC1A unpredictable |
| Typical duty | Lighting ends (obsolete) | Feeders and motors | No RC1A in new designs |
List every RC1A found on patrol into the retrofit plan and replace with RL1 or RT18 after a short-circuit check. Date-mark stocked cartridges, and retire RL1 cartridges after any breaking operation even if intact, since sintered sand degrades the next clearing.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 13539.1 and GB/T 13539.2 (IEC 60269 series) for low-voltage fuse requirements. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.