How do you pick the 65 or 80 percent tap on an autotransformer starter? This page covers the square-law relationship between voltage and torque, a three-step tap selection with a worked example, and changeover timing.
Induction motor torque follows the square of terminal voltage: at 65 percent voltage the starting torque is only 42 percent, at 80 percent it is 64 percent, and current falls roughly in proportion to voltage for a cage rotor at standstill. The 65 percent tap suits light starting loads such as closed-valve pumps and fans, while the 80 percent tap serves heavier or slower starts. The autotransformer is short-time rated, typically two consecutive starts or 60 seconds total, then several hours of cooling.
Tap selection in three steps. First estimate the load torque through the start, say 30 to 50 percent of rated for a closed-valve pump. Second require the motor starting torque at reduced voltage to exceed 1.2 to 1.3 times load torque, giving U/Ue = √(1.3 × TL/Ts). Third pick the nearest standard tap upward. Example: motor starting torque 1.8 times rated, load 0.6 times, so the required ratio is √(1.3 × 0.6/1.8) = 0.66; choose the 80 percent tap for margin, with starting current near 3.4 times rated.
Switch over on speed, not on the clock: when the ammeter falls below about 1.5 times rated or speed reaches 80 to 85 percent, typically 8 to 15 seconds. Open-transition starters give a smaller second inrush than closed-transition ones, which bridge with resistors for heavy loads. Maintenance every six months covers autotransformer insulation, tap bolt torque and contact erosion, replacing tips beyond one-third wear.
| Item | Autotransformer | Star-delta | Note |
|---|---|---|---|
| Tap or wiring | 65 and 80 percent taps | Fixed 1/√3 | More flexible |
| Start torque at 80% | 0.64 of rated | 0.33 of rated | Heavy loads go autotransformer |
| Start current at 80% | About 3.4 times rated | 2~2.4 times rated | Star-delta draws less |
| Motor connection | Any | Delta only | Star-wired motors cannot use it |
| Transition shock | Small, least closed | Second inrush present | Closed transition uses resistors |
| Cost and size | Higher | Lower | Transformer costs |
| Typical use | Medium-large, some load | Light loads, small power | Decide by load torque |
Remember: compute the torque ratio, set the tap, and switch on speed rather than seconds. After maintenance, prove the switching sequence unloaded, because one crossed wire turns the starter into a direct-on-line launch.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 1032 for induction motor testing and IEC 60204-1 for starter safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.