Autotransformer reduced-voltage starters: tap selection and calculation

How do you pick the 65 or 80 percent tap on an autotransformer starter? This page covers the square-law relationship between voltage and torque, a three-step tap selection with a worked example, and changeover timing.

1. How it works

Induction motor torque follows the square of terminal voltage: at 65 percent voltage the starting torque is only 42 percent, at 80 percent it is 64 percent, and current falls roughly in proportion to voltage for a cage rotor at standstill. The 65 percent tap suits light starting loads such as closed-valve pumps and fans, while the 80 percent tap serves heavier or slower starts. The autotransformer is short-time rated, typically two consecutive starts or 60 seconds total, then several hours of cooling.

2. Numbers and practice

Tap selection in three steps. First estimate the load torque through the start, say 30 to 50 percent of rated for a closed-valve pump. Second require the motor starting torque at reduced voltage to exceed 1.2 to 1.3 times load torque, giving U/Ue = √(1.3 × TL/Ts). Third pick the nearest standard tap upward. Example: motor starting torque 1.8 times rated, load 0.6 times, so the required ratio is √(1.3 × 0.6/1.8) = 0.66; choose the 80 percent tap for margin, with starting current near 3.4 times rated.

3. Pitfalls and fixes

Switch over on speed, not on the clock: when the ammeter falls below about 1.5 times rated or speed reaches 80 to 85 percent, typically 8 to 15 seconds. Open-transition starters give a smaller second inrush than closed-transition ones, which bridge with resistors for heavy loads. Maintenance every six months covers autotransformer insulation, tap bolt torque and contact erosion, replacing tips beyond one-third wear.

4. Autotransformer versus star-delta starting

ItemAutotransformerStar-deltaNote
Tap or wiring65 and 80 percent tapsFixed 1/√3More flexible
Start torque at 80%0.64 of rated0.33 of ratedHeavy loads go autotransformer
Start current at 80%About 3.4 times rated2~2.4 times ratedStar-delta draws less
Motor connectionAnyDelta onlyStar-wired motors cannot use it
Transition shockSmall, least closedSecond inrush presentClosed transition uses resistors
Cost and sizeHigherLowerTransformer costs
Typical useMedium-large, some loadLight loads, small powerDecide by load torque

5. Notes

Remember: compute the torque ratio, set the tap, and switch on speed rather than seconds. After maintenance, prove the switching sequence unloaded, because one crossed wire turns the starter into a direct-on-line launch.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 1032 for induction motor testing and IEC 60204-1 for starter safety. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Restarting repeatedly without cooling: the short-time-rated transformer overheats and the insulation fails
② Setting changeover by a fixed timer alone: load changes make the transition early and the second inrush severe
③ Ignoring tap bolt tightness: contact resistance heats the tap leads, from single-phasing to a transformer fire

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.