Chint CJX2 contactor parameters and selection

The CJX2 family is among the most widely used contactor ranges in China. This page decodes the type designation, maps ratings to motor power, and works three sizing examples straight from the catalogue.

1. How it works

The designation CJX2-1810 reads: CJX2 series, 18 A rated working current in AC-3 duty, one NO auxiliary contact. Frames run 9, 12, 18, 25, 32, 40, 50, 65, 80 and 95 A, with coil voltage suffixes such as M7 for AC 220 V and N7 for AC 380 V. Add-on modules include F-series auxiliary contact blocks, matching thermal overload relays and pneumatic timer heads of 0.1 to 30 s.

2. Numbers and practice

Power mapping at 380 V AC-3: 9 A-4 kW, 12 A-5.5, 18 A-7.5, 25 A-11, 32 A-15, 40 A-18.5, 50 A-22, 65 A-30, 80 A-37 and 95 A-45 kW. Examples: an 11 kW pump takes a CJX2-2510; a 15 kW star-delta starter puts one third of the 29 A line current through each contactor, so 18 to 25 A frames serve; a 7.5 kW hoist with frequent inching is AC-4 duty and wants the 32 A frame with the overload checked against AC-4 data.

3. Pitfalls and fixes

Installation and replacement: rail or screw mounting with terminal torques from the datasheet, coil resistance of a 220 V coil on an 18 A frame around 500 to 700 ohms, and pickup noise below 40 dB. Contacts are non-replaceable, so a worn unit changes as a whole, while coils below 40 A frames can be swapped after checking voltage and frequency. Frame dimensions differ between makers at equal ratings, so space spares accordingly.

4. CJX2 selection table at AC-3, 380 V

FrameRated currentMotor powerTypical duty
CJX2-099 A4 kWSmall fans and pumps
CJX2-1818 A7.5 kWGeneral medium loads
CJX2-2525 A11 kWPumps, compressors
CJX2-3232 A15 kWFans, conveyors
CJX2-5050 A22 kWLarge fans
CJX2-9595 A45 kWLarge motor mains

5. Notes

Standardise spares on the 9, 18, 32 and 65 A frames to cut stock variety, label every contactor with the equipment tag and rated current, and always check the AC-3 and AC-4 dual ratings plus the coil voltage suffix before purchase, since coils are not interchangeable across voltage classes.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.4 for contactor product requirements and IEC 60204-1 for installation safety. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Attempting to dress and reuse worn CJX2 contacts: the design is non-replaceable and re-faced contacts weld on the next break
② Sizing star-delta contactors on full line current: each carries one over root three of it, oversizing wastes panel space
③ Mixing coil voltage suffixes: AC 220 V and AC 380 V coils look identical and the wrong one either refuses to pick up or burns

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.