An ESD event can ignite solvent vapour or kill a chip, so how should anti-static grounding be done? This page sets the resistance targets, the floor and wrist-strap chain, and the checks that catch silent failures.
Anti-static earthing differs from protective earthing: the goal is a controlled bleed, with surface-to-earth resistance typically between 10⁵ and 10⁹ ohms depending on the standard applied, not the lowest possible, since too low a path discharges hard enough to spark. This is why tanker unloading uses a grounding clamp with a series resistor. In explosive atmospheres, bonding resistance is kept below about 100 ohms, and when sharing an earth with power or lightning systems the strictest value governs.
The chain: ESD floors and bench mats of 10⁶ to 10⁹ ohms surface resistance, wrist straps through a 1 MΩ current-limiting resistor for personal safety, ESD clothing and footwear keeping the person between 10⁵ and 10⁸ ohms to earth, and conductive castors on carts. Humidity is the cheap half of the programme: below 30 percent relative humidity charge generation soars, so holding 40 to 60 percent beats most hardware.
Verification: quarterly surface-resistance mapping of floors with the standard electrodes, daily wrist-strap tests at the workshop entrance over the full person-strap-earth path near 1 MΩ, and spot checks on mobile equipment. Typical silent failures include waxed-over floors, clips fastened to painted metal, bypassed 1 MΩ resistors and ordinary insoles inside ESD shoes. ESD control is a chain, one insulating link defeats the lot, so audit every link.
| Item | Method | Pass range | Failure result |
|---|---|---|---|
| ESD floor | Surface resistance meter | 10⁵~10⁹ Ω | Charge build-up |
| Bench mat | Surface resistance test | 10⁶~10⁹ Ω | Component damage |
| Wrist strap system | Person-strap-earth total | About 1 MΩ ±20% | Charged operator zaps parts |
| Series resistor | Check 1 MΩ in place | Not shorted | Spark risk |
| ESD shoes | Body-to-earth resistance | 10⁵~10⁸ Ω | Bleed path broken |
| Humidity | Hygrometer | 40~60% RH | Low humidity surge |
Keep an ESD ledger for assembly and solvent-filling areas with quarterly full coverage, put the strap tester at the entrance so staff test before entering, and verify the anti-static rating of any floor coating or wax before it quietly wrecks the system.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See SJ/T 10694 for ESD control in electronics manufacturing and IEC 60204-1 for machinery electrical safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.