Repeated earthing in TN systems and the resistance values that matter

Repeated earthing is the last line of defence in a TN system - it caps fault voltage and saves the day when the neutral breaks. This page covers where to install it, what resistance to demand, and how to test honestly.

1. How it works

Repeated earthing means connecting the PEN or PE conductor to earth not only at the transformer neutral but along the route. It lowers touch voltage during a frame fault, stabilizes the neutral if the PEN breaks (preventing phase-voltage excursions), and evens out potential during lightning induction. Required locations: every kilometre or so on overhead mains, at cable terminations, at building entries, and wherever PEN splits into PE and N.

2. Practice and pitfalls

Values: a single repeated earth electrode is generally ≤10Ω, parallel with the 4Ω working earth of the transformer. Measure with a three-pole earth tester (auxiliary electrodes 5 to 10m away) or a clamp-type tester; wet-soil readings run low, dry season high - allow seasonal margin. Workmanship traps: water pipes are forbidden as the sole electrode (plastic sections break the path), welded lap joints must meet the code (flat steel twice its width, round steel six times its diameter), and bolted terminals need anti-loosening hardware. Number, archive and retest every earthing point before each storm season.

3. Earthing resistance quick table

Earthing typeResistance limitTest methodInterval
Transformer working earth≤4ΩThree-pole fall-of-potentialYearly
Repeated earth (single)≤10ΩThree-pole or clampYearly, pre-storm
TT protective earthRA × IΔn ≤ 50VThree-poleYearly
Lightning protection1~30Ω by classThree-polePre-storm season
Data room combined≤1Ω (when specified)Three-poleYearly
ESD earthing≤100ΩEarth testerAs required

4. Notes

Checklist: earth at building entry, at the PEN split and at line ends; test all points before storm season and file the numbers; weld laps to code and lock bolted terminals. Water pipes are not a plan.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Earthing design per GB/T 50065; installation and acceptance of earthing per GB 50169. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Water pipe as the only electrode:plastic sections break the path, fault voltage stays high
② Spot-welded earth joints:corroded through in a few years, the electrode becomes decoration
③ Testing only the new rod:corroded system connections stay hidden

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.