Why does the drive trip on overvoltage when decelerating without a braking resistor? This page traces the regenerated energy, derives resistance and power ratings, and works a 15 kW example from start to finish.
During deceleration the motor acts as a generator, pushing energy back through the freewheeling diodes into the DC bus and charging the capacitors: a 380 V system rides near 540 V and trips on overvoltage around 660 to 700 V. The braking unit switches a resistor across the bus above its threshold, burning the energy as heat. Braking resistors are needed for fast stops, overhauling loads such as hoists, and reversing duty.
Derive the braking torque from inertia and deceleration time, convert to peak braking power, then apply R = U²/P with U taken as 660 V on a 380 V system. Example: a 15 kW drive with 0.8 kg·m² total inertia stopping from 1480 r/min in 1 second peaks near 37.5 kW, giving R = 660²/37500 ≈ 11.6 ohm; a standard 13.6 ohm bank fits the unit current limit. Average power follows the duty cycle: braking 2 s every 20 s yields about 2.6 kW, so a 3 kW resistor bank with 30 percent margin is right.
Three selection rules: never below the minimum resistance or the unit blows its transistors, not above twice it or braking torque suffers, and average power with 30 percent headroom. Install the resistor bank in its own ventilated enclosure away from control wiring, use heat-resistant cabling within 10 m, and wire a thermal switch for over-temperature protection. For continuous overhauling duty prefer a regenerative unit that returns energy to the mains.
| Drive power | Resistance range | Unit current | Typical bank |
|---|---|---|---|
| 5.5 kW | 40~80 ohm | Up to 15 A | 4 × 300 W parallel |
| 11 kW | 20~40 ohm | Up to 25 A | 4 × 500 W series-parallel |
| 15 kW | 12~27 ohm | Up to 48 A | 3 kW bank or 10 × 300 W |
| 30 kW | 7~13 ohm | Up to 80 A | External unit plus bank |
| 55 kW | 4~8 ohm | Up to 150 A | Prefer regeneration |
| Above 90 kW | 2.5~5 ohm | Per unit | Regeneration advised |
Practical commissioning: start with a 10 second ramp, shorten until just before the overvoltage trip, then size the resistor from the measured duty. Check the bank temperature and terminal torque quarterly; a glowing resistor is the next fire risk.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 12668.2 for VFD requirements and IEC 60204-1 for safety of the drive system. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.