Selecting conductor cross-section by allowable voltage drop

Why does a distant motor sag badly at start, and how large must the cable be? This page walks the four-step cross-section method with a worked 380 V long-distance motor example.

1. How it works

Drop limits by rule: 5 percent for motor circuits in normal running with terminal voltage not below 85 to 90 percent of rated during starting, and 5 percent for lighting. Three-phase drop follows ΔU% = √3·I·L·(R·cosφ + X·sinφ)/U × 100. A handy form for 380 V copper at cosφ 0.8 is ΔU% ≈ 0.32 × I × L/(100 × S), with aluminium about 1.7 times worse.

2. Numbers and practice

Four steps: first pick a section by ampacity with installation and temperature correction, for example 30 A in conduit needs 10 mm² copper once the 0.8 grouping factor applies; second verify the running drop; third check thermal short-circuit withstand against the protective clearing time; fourth confirm mechanical minimums of 1.5 mm² copper and economic current density. Take the largest result of the four.

3. Pitfalls and fixes

Worked example: a 55 kW, 103 A motor 300 m away with 5 percent allowed. A 70 mm² copper core carries the load and gives about 1.4 percent running drop, but starting at six times current yields 8.5 percent, terminal voltage 91.5 percent, barely inside until you add the 3 percent already lost upstream, which forces 95 and then 120 mm² or a larger transformer. Starting drop dominates on long runs, which surprises people who only checked ampacity.

4. Cross-section verification checklist

CheckLimitBasisIf not met
AmpacityLoad times factorsInstallation, temperatureUpsize
Running drop5 percent maxLine impedanceUpsize or raise voltage
Starting dropTerminal above 85~90%Starting currentUpsize or soft start
Short-circuit heatWithstand to clearingProtection timeBigger cable, faster trip
Mechanical1.5 mm² copper minCode minimumApply minimum
EconomicsEconomic densityUtilisation hoursCompare overall

5. Notes

After calculating a long run, always stack the starting drop onto the upstream transformer and feeder losses, and catch the actual inrush with a recorder at the motor: a gap against calculation usually means a hidden high-resistance joint waiting for the next outage.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 50054 for LV distribution design and the GB/T 16895 series for cable ampacities. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Sizing a long feeder on ampacity alone: terminal voltage collapses to 80 percent at start, torque dies and the overload trips repeatedly
② Ignoring conduit and grouping corrections: a 32 A cable really carries 25 A in a bundle and ages hot
③ Forgetting upstream impedance in the start check: 3 percent at the transformer tips an acceptable result below 85 percent

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.