A three-phase motor burns fastest on single-phasing, yet an ordinary thermal relay sometimes fails to protect it. This page explains the differential mechanism and where phase-failure relays are mandatory.
When a phase opens, the two remaining lines carry 1.7 to 2 times rated while the lost phase shows zero. With a plain three-element relay set at rated current, heavy loads do trip, but under light load the surviving lines may carry only 1.1 to 1.3 times rated, and the relay never acts while the winding cooks for hours. Delta-connected motors are the worst case: internal winding currents redistribute in ways the line-side elements only partly see.
Phase-failure designs such as JR36 add a differential guide and lever: with balanced three-phase heating the three bimetal strips bend together and the guide moves parallel without acting. On phase loss one strip cools and straightens while the other two bend further, producing differential travel that rotates the lever and amplifies the displacement, so the relay trips within minutes even at 1.05 times setting. Standards define the phase-loss characteristic separately for star and delta machines.
Selection: differential-type relays are mandatory for delta-connected machines above 3 kW, unattended equipment and critical lines. Set the current at 0.95 to 1.05 times the motor nameplate, never at the contactor rating; prefer manual reset on heavy plant so a fault cannot restart repeatedly, and verify annually with a primary injection set: trip within 20 minutes at 1.2 times, within 3 minutes at 1.5 times, and hold above 5 seconds at 6 times starting current.
| Motor case | Recommended type | Setting | Note |
|---|---|---|---|
| Delta above 3 kW | Phase-failure type | 0.95~1.05 of rated | Mandatory |
| Star, small power | Plain three-phase acceptable | 0.95~1.05 of rated | Loss current ratio is high |
| Unattended plant | Phase-failure + manual reset | Per nameplate | Prevents restarts |
| Heavy-start duty | Phase-failure + delayed | Per start curve | Ride through starting |
| Below a VFD | Prefer electronic protection | Per drive output | Low-frequency behaviour differs |
| Two-speed motor | One per winding | Per speed rating | Protect each speed |
Audit the plant relay list and change every plain relay on a delta motor to a phase-failure type. Log the setting against the nameplate after each replacement and prove the function once with a simulated single-phase pulse during commissioning.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.4 for thermal relay requirements and IEC 60204-1 for protection coordination. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.