Why do LV main boards use air circuit breakers instead of moulded cases at the transformer outlet? This page covers ACB construction, the four-zone protection logic, selectivity grading and drawout cradle maintenance.
ACBs carry 630 to 6300 A with breaking capacities of 65 to 150 kA and sit at the transformer LV outlet and bus-tie positions. Their short-time withstand of 50 to 85 kA for 1 second allows time-graded selectivity with downstream moulded-case breakers, so only the faulty feeder trips. Electronic trip units provide long-time overload, short-time, instantaneous and ground-fault zones, plus metering and communication for current, voltage and harmonics.
Set the zones from the source down: long-time at 1.05 to 1.2 times transformer current with an inverse-time curve; short-time above the largest downstream fault current with a 0.1 to 0.4 s delay, commonly 0.3 s, to form the grading step; instantaneous either well above the bus fault level or disabled on incomers to preserve selectivity; ground fault at 20 to 100 percent of rated with 0.1 to 0.4 s. A typical scheme runs the incomer with instantaneous off and 0.4 s short-time, feeders instantaneous, so any fault clears at one point only.
Drawout gear: the TEST position energises controls with contacts open, the ISOLATED position allows safe work. Annual checks cover contact wear beyond 2 mm, spring condition, mechanism lubrication every two years, and cradle rail or racking-motor problems that stall mid-stroke. Verify control voltage and undervoltage release before closing, or the breaker will refuse or misbehave on a voltage recovery.
| Item | ACB | MCCB | Note |
|---|---|---|---|
| Rated current | 630~6300 A | 16~1600 A | Position dependent |
| Breaking capacity | 65~150 kA | 35~100 kA | ACB stronger |
| Short-time Icw | 50~85 kA/1 s | 10~20 kA/1 s | Key to selectivity |
| Protection zones | Four, intelligent | Two or three | ACB grades delays |
| Mounting | Drawout | Fixed or plug-in | Easier maintenance |
| Typical position | Transformer outlet, bus-tie | Feeders | Coordinated pairs |
Check the setting sheet against the calculation before energising a new board, and run annual mechanical-characteristic tests: closing and opening times and pole synchronism, archived against last year and investigated when any value drifts beyond 20 percent.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.1 for low-voltage switchgear general rules and GB/T 14048.2 for circuit breaker requirements. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.