Fans, crushers and compressors take 15 to 30 seconds to spin up, tripping a Class 10 relay at every start. Here is how to match trip class, starting method and measured starting time.
Trip classes are defined by time to trip at 7.2 times the setting: Class 10 operates within about 10 seconds, Class 20 within 20, Class 30 within 30. A direct-on-line centrifugal fan draws 6 to 7 times rated current for 15 to 25 seconds, so fit Class 20 or 30, or switch to an electronic relay with an adjustable class and phase-loss protection.
Measure the real starting time with a peak-hold clamp meter, add 5 seconds of margin, and pick the class above that line. Star-delta starting cuts inrush to 2 to 2.5 times rated and lets a Class 10 survive, but with only a third of the torque it will not start constant-torque loads. With a VFD, rely on the drive electronic protection instead of a bimetal on the output side.
| Starting method | Inrush multiple | Suggested class | Notes |
|---|---|---|---|
| Direct on line | 6~7x | Class 20/30 | Class 10 only if unloaded in 10s |
| Star-delta | 2~2.5x | Class 10 | Careful with constant torque |
| Autotransformer | 3~4x | Class 20 | Watch transition surge |
| Soft starter | 2~4x adjustable | Class 10 | Normal after bypass |
| VFD driven | 1~1.5x | Drive electronic protection | Skip the output bimetal |
| Heavy fans, crushers | 6~7x long | Class 30 or electronic | Measure starting time first |
Never copy a table without measuring: log one real start with a peak-hold clamp meter, add 5 seconds, and choose the class above that. If nothing fits, an electronic relay covers overload, phase loss and stall in one unit.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor starting and protection per GB/T 755; overload relays per GB/T 14048.4; machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.