Beyond the main contacts, a breaker carries a row of small terminals: auxiliaries, shunt trip, undervoltage release. This page explains what each does, how to wire them, and classic interlock applications for control design.
Auxiliary contacts move with the main contacts, typically 2 to 4 NO and NC pairs rated 3 to 6 A, feeding breaker status to the control system: closed indication, trip alarm, spring charged, racking position. A common block locks the closing circuit until spring charging completes. Mind the small rating: drive contactor coils through an interposing relay, never directly from an auxiliary contact.
The shunt release is a short-time coil that trips the breaker within 0.05 to 0.3 s of energising, used for remote tripping and fire-alarm power shedding at AC 220 V or DC 110/220 V; energising beyond about 1 s burns the coil unless the type has self-cut. The undervoltage release works the other way, tripping when voltage falls below 35 to 70 percent of rated, and needs continuous energisation, so a blown fuse in its voltage circuit trips the whole board, a classic cascade-avoidance trap.
Interlock examples: bus-tie versus two incomers electrically blocked against paralleling; fire alarm in series with shunt trips of non-fire feeders; transformer room door switch in the undervoltage circuit so opening the door kills the board. Test shunt releases yearly in the TEST position between 70 and 110 percent of rated voltage, check undervoltage trips below 35 percent, and verify auxiliary contact agreement with the main contacts with a meter, since a poor contact breeds false alarms.
| Accessory | Operating condition | Typical use | Caution |
|---|---|---|---|
| Auxiliary contacts | Move with main contacts | Status, indication, PLC input | 3~6 A, use interposer |
| Shunt release | Pulse energise to trip | Remote trip, fire shedding | Short-time, no sustained feed |
| Undervoltage release | Below 35~70% voltage | Loss-of-voltage protection | Needs continuous supply |
| Charged-spring contact | Spring fully charged | Blocks closing until ready | Required for motorised units |
| Alarm contact | Trip-unit fault flag | Separates faults from normal open | Wire to alarm system |
| Racking position switch | Service/test/isolated | Position interlock and monitoring | No closing unless home |
Draw the accessory wiring with terminal numbers before building the panel and match coil voltage classes to the control supply. Put accessory operation in the annual test list and log operating voltages to trend degradation.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.2 for breaker accessories and IEC 60204-1 for control circuit design. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.