An open CT secondary really does produce kilovolt spikes - it is not a scare story. This page explains the current-source behaviour behind it and the safe shorting procedure for removing a meter under load.
A CT secondary is wired in series with meters and relays, and behaves as a current source: primary current is set by the load circuit, not by the secondary. Normally the secondary ampere-turns cancel the primary, leaving a tiny core flux and a few volts across the secondary. Open the circuit and the cancelling current vanishes - all primary current becomes magnetizing current and the core saturates hard.
The collapsing flux induces narrow spikes of 3 to 5kV across a 400/5 CT secondary. Consequences: arcing terminals and shock hazard, core losses that push the temperature past 100 degrees within minutes, and permanent remanence that degrades accuracy for good. Before removing a meter, bolt a shorting bar across K1-K2 at the terminal block, verify it, and only then open the circuit; restore the meter first and remove the short last. One earth point on K2 is mandatory.
| Secondary state | Secondary voltage | Core state | Risk |
|---|---|---|---|
| Normal rated burden | A few volts | Small net flux | Safe, accurate |
| Overrated burden | Slightly higher | Mild saturation | Metering error grows |
| Open-circuit instant | 3~5kV spikes | Deep saturation | Shock, arcing, burnt coil |
| Open circuit sustained | Sustained spikes | Over 100 degrees C | Insulation charred, remanence |
| Shorted running | Near zero | Like normal | Safe, no meter reading |
| K2 not earthed | Normal few volts | Normal | Primary fault feeds the meters |
One line to remember: a CT secondary is either closed or shorted, never open. Short first, disconnect second; connect the meter first, remove the short last. The order is the whole safety case.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Current transformer requirements per GB/T 20840.1 (IEC 61869 series); installation safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.