Why a current transformer secondary must never run open

An open CT secondary really does produce kilovolt spikes - it is not a scare story. This page explains the current-source behaviour behind it and the safe shorting procedure for removing a meter under load.

1. How it works

A CT secondary is wired in series with meters and relays, and behaves as a current source: primary current is set by the load circuit, not by the secondary. Normally the secondary ampere-turns cancel the primary, leaving a tiny core flux and a few volts across the secondary. Open the circuit and the cancelling current vanishes - all primary current becomes magnetizing current and the core saturates hard.

2. Practice and pitfalls

The collapsing flux induces narrow spikes of 3 to 5kV across a 400/5 CT secondary. Consequences: arcing terminals and shock hazard, core losses that push the temperature past 100 degrees within minutes, and permanent remanence that degrades accuracy for good. Before removing a meter, bolt a shorting bar across K1-K2 at the terminal block, verify it, and only then open the circuit; restore the meter first and remove the short last. One earth point on K2 is mandatory.

3. CT secondary states and risks

Secondary stateSecondary voltageCore stateRisk
Normal rated burdenA few voltsSmall net fluxSafe, accurate
Overrated burdenSlightly higherMild saturationMetering error grows
Open-circuit instant3~5kV spikesDeep saturationShock, arcing, burnt coil
Open circuit sustainedSustained spikesOver 100 degrees CInsulation charred, remanence
Shorted runningNear zeroLike normalSafe, no meter reading
K2 not earthedNormal few voltsNormalPrimary fault feeds the meters

4. Notes

One line to remember: a CT secondary is either closed or shorted, never open. Short first, disconnect second; connect the meter first, remove the short last. The order is the whole safety case.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Current transformer requirements per GB/T 20840.1 (IEC 61869 series); installation safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Opening the secondary live:3~5kV arcs, burnt coil, permanent accuracy loss
② A loose shorting link:contact resistance keeps the circuit from truly shorting
③ Missing earth on K2:a primary insulation fault feeds kilovolts into every meter

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.