Short-circuit protection must be fast, must actually interrupt, and must not trip the whole plant. This page explains current limiting and how to verify coordination between fuse levels.
A fuse's superpower is current limiting: the element clears within milliseconds, before the prospective fault current reaches its peak. On a circuit with a 20kA prospective current, a 100A gG fuse may let through only 8 to 10kA for under 5ms - a fraction of the I²t the cable could have suffered. The other line of defence is breaking capacity: it must exceed the prospective short-circuit current at that point, or the fuse bursts trying.
Selectivity keeps the outage local: rate upstream links at least 1.6 times downstream (160A over 100A over 63A) and verify that the downstream total I²t (pre-arcing plus arcing) stays below the upstream pre-arcing I²t. One-step differences (125A over 100A) sit on top of each other at high currents and trip both levels - overlay the curves to see it. Mixed systems: fuses back up breakers whose 6kA rating falls short of a 20kA bus, and contactors rely entirely on the fuse for short circuits (type 1 or type 2 coordination). Wire the striker indicators into the alarm circuit so a blow is located in seconds.
| Check | Requirement | Method | If violated |
|---|---|---|---|
| Rating step | 1.6x or more between levels | Compare curves | Nuisance trips upstream |
| Downstream total I²t | Below upstream pre-arcing I²t | Datasheet tables | Both levels blow together |
| Breaking capacity | Above prospective current | System study | The tube bursts |
| Contactor pairing | Type 1 or type 2 | Coordination tables | Welded contacts |
| Striker circuit | Wired to alarm/interlock | Drawing check | Blows go unnoticed |
| Spares consistency | Match the drawings | Parts list audit | Selectivity destroyed |
Workflow: compute the prospective current, pick a breaking-capacity-compliant fuse, step ratings 1.6 times per level, prove selectivity by curve or I²t, and wire the indicators. Four steps and the protection is real.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage fuses per GB 13539.1 (IEC 60269-1); fuse-contactor coordination per GB/T 14048.4; LV design per GB 50054. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.