Constant-torque versus constant-power loads: tell them apart before sizing

Conveyors, winders and machine spindles load a drive in completely different ways. This page defines the three classic load families, shows how to identify them by measurement, and lists the sizing consequences of getting it wrong.

1. How it works

Constant-torque loads need the same torque at any speed with power rising with speed: belt conveyors, hoists, screw compressors and extruders. Constant-power loads trade torque against speed at near-constant power: winders holding tension as the roll grows, and machine spindles that cut hard and slow or finish fast. Fan and pump loads scale torque with the square and power with the cube of speed, so slowing 20 percent cuts power to 51 percent. Measure torque at several speeds and the family is obvious.

2. Numbers and practice

Sizing: for constant-torque duty cover the maximum load torque plus acceleration with 1.3 to 1.5 margin, and watch self-ventilated machines below about 20 r/min where cooling collapses, requiring forced ventilation or a bigger frame. Constant-power sizing fixes the motor by the torque needed below base speed, with field weakening typically limited to twice base speed. Fans and pumps size the converter on rated current without oversizing, operated at the efficient part of the curve.

3. Pitfalls and fixes

Typical misjudgements: treating a winder as constant torque trips the drive at large roll diameter at low speed; a spindle stalling in heavy low-speed cuts means the constant-power band reaches too far down, so add a gearbox or pick a wider constant-torque range; and a fan retrofit that saves less than promised usually has dampers still throttling. Half a day measuring the load curve beats a hundred-fold rework later.

4. Load families and sizing points

FamilyTorque-speed lawTypical dutySizing note
Constant torqueT flat, P follows speedConveyor, hoist, extruder1.3~1.5 margin, cooling at low speed
Constant powerT inverse to speedWinder, spindleSize below base speed, weaken to 2x
Fan and pumpT with speed squaredCentrifugal fan, pumpNo converter oversizing
CombinedCT low, CP highPaper section drivesCheck torque per band
Potential energyFour-quadrantLifts, cranesBraking unit mandatory
Shock loadViolent torque swingsCrushers, pressesPeak torque and flywheel check

5. Notes

Measure first, then select; draw the curve before the capacity. Where the family is unclear, size conservatively as constant torque, half a frame up rather than half a frame down.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 12668 for adjustable-speed drive sizing and GB/T 755 for motor ratings. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Sizing a winder as constant torque: low speed with a full roll overloads the drive again and again
② Running self-ventilated motors below 20 r/min without derating: airflow is gone and the winding heats quietly
③ Retrofitting fans without interlocking the dampers: savings collapse from 40 to 10 percent and the investment looks pointless

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.