Active, reactive and apparent power explained with the power triangle

kW, kvar and kVA get mixed up daily - and the mix-up costs cable area, transformer size and penalty fees. This page draws the power triangle and works a real compensation example.

1. How it works

Apparent power S = UI in kVA is what cables and transformers must carry; active power P = UIcosφ in kW does the work and runs the meter; reactive power Q = UIsinφ in kvar shuttles between source and load to build magnetic fields. They form a right triangle, S² = P² + Q², and the utility bills penalties below 0.9 power factor.

2. Practice and pitfalls

Example: a 380V 10kW motor at cosφ = 0.86 draws S = 11.6kVA, I ≈ 17.7A. Let the power factor sag to 0.7 and the same 10kW needs 14.3kVA and 21.7A - 50 percent more line loss from I²R. Compensation: Qc = P×(tanφ1 − tanφ2), so 10kW from 0.86 to 0.95 needs about 2.6kvar. Size everything - cables, transformers, breakers - in kVA, never kW. Local compensation follows 90 percent of the motor magnetizing reactive power; overcompensation raises voltage, and harmonic-rich boards need detuned reactors or the cans cook.

3. Power quantities and compensation quick table

QuantityUnitFormulaGoverns
Apparent SkVAS = √3 × U × ICable, transformer, breaker sizing
Active PkWP = S × cosφReal work, energy metering
Reactive QkvarQ = S × sinφMagnetization, compensation
Power factorNonecosφ = P/SUtility penalty below 0.9
Compensation QckvarP × (tanφ1−tanφ2)2.6kvar for 10kW to 0.95
Local cap sizingkvar0.9 × magnetizing QPrevents self-excitation

4. Notes

Practice: when plant power factor sags below 0.9, audit lightly loaded large motors first - they are the reactive hogs. Bulging compensation cans point to harmonics; detuning reactors beat can-swapping. Every capacity decision is billed in kVA.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality requirements per GB/T 15543 and GB/T 12325; reactive compensation per GB/T 15576. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Sizing cables on kW:current follows kVA, undersized copper overheats
② Local capacitors sized by motor rating:self-excitation overvolts the motor at switch-off
③ Bare capacitors on harmonic boards:amplified harmonics cook cans monthly

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL